| Power supply and I/O Specifications | Power supply | 100 to 240 V AC (AC power), 24 V DC (DC power) |
|---|
| Input | 24V DC °C common |
|---|
| Output | 2 A | 0.5 A |
|---|
Service power supply (AC power type only) | 0.15 A (C14)/ 0.4 A (C30/ C60) |
|---|
| Performance Specifications | Number of I/O points | C14 | Input: 8 points, Output: 6 points |
|---|
| C30 | Input: 16 points, Output: 14 points |
|---|
| C60 | Input: 32 points, Output: 28 points |
|---|
| I/O points when expanded | C14 | Max. 328 points (When using FP0 expnasion unita and add-on cassette) |
|---|
| C30 | Max. 352 points (When using FP0 expnasion unita and add-on cassette) |
|---|
| C60 | Max. 382 points (When using FP0 expnasion unita and add-on cassette) |
|---|
| Operation speed | 0.32μs/step |
|---|
| Program memory | Flash ROM built-in (no battery backup required) |
|---|
| Program capcity | 16 ksteps (C14), 32 ksteps (C30, C60) |
|---|
| Basic instructions | 111 |
|---|
| Applied instructions | 216 |
|---|
| Operation memory | Internal relay ® | 4096 points |
|---|
| Timer/counter (T/C) | 1024 points |
|---|
| Data register (DT) | 256 words |
|---|
| Special functions | Pulse catch input | 14 points | 14 points |
|---|
| Interrupt input | 14 points | 14 points |
|---|
| Analog I/O | Input: Max. 24 ch, Output: Max. 12 ch (When using FP0 analog unit) Input: Max. 4 ch (When using add-on cassette) |
|---|
| Volume input | 2 points (C14/C30), 4 points (C60) |
|---|
| High-speed counter | Input of main unit | Single-phase: 8 ch x Max. 10 kHz 2-phase: 4 ch Max. 5 kHz | Single-phase: 8 ch (High-speed: 4 ch, midium-speed: 4 ch) 2-phase: 4 ch (High-speed: 2 ch, midium-speed: 2ch)With high-speed single-phase: 1 ch x Max. 100 kHz 2 ch x Max. 80 kHz 3 ch x Max. 60 kHz 4 ch x Max. 50 kHz With high-speed 2-phase: 1 ch x Max. 35 kHz 2 ch x Max. 25 kHz With medium-speed single-phase: 4 ch x Max. 10 kHz each With Medium-speed 2-phase: 2 ch x Max. 5 kHz each |
|---|
| when pulse I/Ocassette installed | Single-phase: 2 ch x Max. 80 kHz, 4 ch x Max. 50 kHz 2-phase: 1 ch x Max. 30 kHz, 2 ch x Max. 25 kHz | Pulse I/O cassette cannot be installed. |
|---|
| Pulse output | Input of main unit | – | With high-speed 2 ch x Max. 100 kHz For linear interpolation, compositespeed: 100 kHz With medium-speed 2 ch x Max. 20 kHz For linear interpolation, compositespeed: 20 kHz |
|---|
| when pulse I/Ocassette installed | 1 ch x Max. 100 kHz, 2ch x Max. 80 kHz | Pulse I/O cassette cannot be installed. |
|---|
| Serial interface | RS232C.RS485, USB, Ethernet |
|---|
| Network function | PLC Link, Computer link, Modem, Modbus-RTU |
|---|
| Other functions | Program editing during RUN, Constant scan, 8-digit password, Program |
|---|