| △Measuring range: | -500-500Pa~0-31MPa |
| △Output: | HART signal superimposed on 2-wire, 4 – 20mA |
| △Accuracy: | Gauge pressure: ±0.1%FS(optional 0.2, 0.5) |
| △Temp. effect: | ±(0.3%URL+0.3% of F.S.) |
| △Stability: | ±0.1%URL |
| △Mounting position effect: | Zero drift ≤0.3Kpa,(can be calibrated out) |
| △Vibration effect: | < ±0.1%URL |
| △Power effect: | <0.01/% of F.S. |
| △Power supply: | 12…30VDC |
| △Load: | Max. load resistance R: R=(V-12V) / 0.023. R: Max. Load resistance Ω. V: Power voltage. |
| △Initialization time: | 2Sec |
| △Refresh time: | 0.25Sec |
| △Zero and span adjust: | Through menu or HART communicator. |
| △Failure mode alarm: | If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 3.8 mA or to 20.8 mA to alert the user. High or low alarm signal is user-selectable by HART communicator. |
| △Damping const: | Selectable time constant between 0 and 32s. |
| △Operating temp. | -35…80℃ |
| △Medium temp. | -25…85℃ |
| △Storage temp. | -40…125℃ |
| △Relative humidity: | 5%-98% |
| △Protection class: | IP65 |
| △Material: | Electronics housing: Aluminum Alley |
| △Process connect. | G1/2,M20X1.5 male thread. |
| △Electrical connect. | M20 x 1.5 threaded conduit entries. |
| △Weight: | 4.9kg(No accessories) |
| △Impulse piping: | “High” side connecting hole: 1/4-18NPT “Low” side connecting hole: 1/2-14NPT. |