| △Measuring range: | -250-250Pa~0-31MPa |
| △Output: | HART signal superimposed on 2-wire, 4 – 20mA |
| △Accuracy: | Gauge pressure: ±0.075%FS* (Optional 0.2, 0.5) |
| △Temp. effect | ≤±0.45%/55℃ |
| △Static press. Effect | ±0.1%/7Mpa(Zero), ±0.2%/7Mpa(span) |
| △Stability: | No more than accuracy in 6 months) |
| △”Zero” Error: | Model DP: zero error: ±0.5% of upper range limit. (Can be calibrated out) |
| Model HP: zero error: ±1% of upper range limit. (Can be calibrated out) |
| △Measuring error: | ±0.25% of measuring pressure(Can be calibrated out) |
| △Mounting position effect: | An up to 0.24Kpa error can be expected if the diaphragm is not in vertical plane, which can be calibrated out. |
| △Vibration effect: | ±0.1% of upper range limit. |
| △Power effect: | Less than ±0.005% of calibrated span per volt. |
| △Power supply: | 12…30VDC |
| △Static pressure & overpressure limit: | Model LP:1-4Mpa; Model DP:0-13Mpa; Model HP:0-31Mpa. |
| △Load resistance: | Max. load resistance R: R=(V-10.5) / 0.0236. R: Max. Load resistance Ω. V: voltage. |
| △Initialization time: | 5Sec |
| △Refresh time: | 0.25Sec |
| △”Zero” and span adjusting: | Through menu or HART communicator. |
| △Positive / Negative suppression: | Max. positive suppression: difference between upper range limit(URL) and calibrated range. |
| △Failure mode alarm: | If self-diagnostics detect a gross transmitter failure, the analog signal will be driven either below 3.8 mA or to 20.8 mA to alert the user. High or low alarm signal is user-selectable by HART communicator. |
| △Damping: | Selectable time constant between 0 and 32s. |
| △Operating temp. | Electrical parts: -30…85℃. Sensing components(Silicone oil fill): -40…104℃. Sensing components(inert oil fill): -0…70℃ |
| △Ambient temp. | -40…104℃ |
| △Storage temp. | -40…125℃ |
| △Relative humidity: | 5%-98% |
| △Protection class: | IP65 |
| △Materials: | Electrical parts housing: aluminum alloy. See order code for other material for others. |
| △Process connection: | Connecting hole of pressure chamber:1/4-18NPT, Connecting hole of impulse pipe: 1/2-14NPT. |
| △Electrical connect. | M20 x 1.5 threaded conduit entries. |
| △Weight: | 4.9kg (No accessories) |